274C 100 kW Generator Head
PDG 274C 100 KW
Auxiliary Boost Winding (150% boost of rated power for 5 seconds)
AVR AS440
Winding 311 – 12 Wire 3PH (277/480V)
Class H Insulation
60 HZ
4 Pole 1800 RPM
.8 Power Factor
Temp Rise/Ambient (125/40)
Unit Weight: 960lbs.
Single Bearing (direct connect through SAE bellhousing & flywheel)
143HP Diesel engine required for full output, may use engine with less HP but will not produce full output
200HP Gas engine required for full output, may use engine with less HP but will not produce full output
Three Phase Wiring Options
120/240 1 Phase
120/240 3 Phase
120/208 3 Phase
277/480 3 Phase
When purchasing a 3 phase (277/480V) generator, you can opt to have it rewired to one of the above options, otherwise, 3 phase generators come standard 277/480V. If you need your 3 phase generator rewired to one of the options above, please let us know when placing your order. Please keep in mind that a 3 phase generator rewired to dedicated single phase 120/240V will lose 1/3 of its power.